AH 5 00 Mo d u le Ma n ua l
The display mechanism of the digital display:
1. When AH10PFBM-5A is in normal state and PLC is in RUN state, the digital display of
AH10PFBM-5A only displays the node address.
2. When AH10PFBM-5A is in normal state and PLC is in STOP state, the digital display of
AH10PFBM-5A displays the node address and 80 (the STOP state code of PLC)
alternately.
3. When AH10PFBM-5A is in error state, the digital display of AH10PFBM-5A displays the
error code.
4. When the slave is offline and PLC is in RUN state, the display of AH10PFBM-5A displays
E2 and the node address of the offline slave alternately. For example, E2, 02, E2 and 03
appear in a cycle, which means the slaves of No. 2 and No.3 are offline.
5. When the slave is offline and PLC is in STOP state, the display of AH10PFBM-5A displays
80 (the STOP state code of PLC), node address of the master, E2 and node address of the
offline slave. For example, 80, 01, E2, 02, 80, 01, E2 and 03 appear in a cycle, which
means PLC is in STOP state; the node address of the master is 1 and the slaves of No. 2
and No. 3 are offline.
6. When many errors occur in the master, only the high-priority error code is shown. The error
codes are F7, F6, F3, F4, F8, F5, F1, E2/80, F2 and FB in order of priority from high to low.
E2 and 80 have the same priority. If the two errors occur simultaneously, the display will
show E2 and 80 alternately.

12.7.3 Registers in Normal Exchange Area in AH10PFBM-5A

The registers in the normal exchange area in AH10PFBM-5A display if the current state of the
PROFIBUS DP network is normal.
Click the following place marked in pink box; the "Manual Assignment" dialog box appears, where
set the starting number of the register in the normal exchange area while configuring the hardware
in the ISPSoft software.
1 2 - 5 4