AH 5 00 Mo d u le Ma n ua l

10.3.2 Connecting to the DeviceNet Communication Connector

1. After wiring is completed, insert the DeviceNet connector to the port.
2. Tighten the screws on two sides of the DeviceNet terminal.

10.3.3 DeviceNet Bus Network Topology Structure

The transmission distance on the DeivceNet bus network is determined by the transmission rate.
The following table shows the corresponding maximum communication distance at different baud
rates.
Baud rate (Bit/s)
10K
20K
50K
125K
250K
500K
800K
1M
Max. transmission
5000
2500
1000
500
250
100
50
25
distance (M)
1 0 - 8