Download Print this page

Load & Motor - Trane VarioTrane TR1 2800 Series Operating Instructions Manual

Advertisement

The following tables show the application specific parameter settings for Trane equipment that utilizes the
TR1 2800 Extended Temperature hardware version. Listed are settings for Trane rooftop unitary equipment and
Trane CGAM AquaStream ™  chillers.
Parameter
102
103
LOAD & MOTOR 
105
106
209
210
211
REFERENCES & 
LIMITS
212
226
Table 7. 1: Trane rooftop unitary equipment
130
Description
Standard factory
default setting
Motor Power
1.1 kW
For 200 V units: 230 V
Motor Voltage
For 400 V units: 460 V
Motor Current
2.7 A
Rated Motor Speed
1140 RPM
Ramp Up Time 2
3.00 seconds
Ramp Down
3.00 seconds
Time 2
Jog Ramp Time
10.00 seconds
Quick-Stop
10.00 seconds
Ramp Down Time
Warning: High
132.0 Hz
Frequency
Rooftop settings
Based on motor
Based on motor
Based on motor
Based on motor
10.00 seconds
10.00 seconds
3.00 seconds
3.00 seconds
120.0 Hz
TR1 2800 Series VFD