u Subchart A-1: Simple Motor Setup Using V/f Control
Flowchart A1 in
Figure 4.8
illustrates Energy Savings and Speed Estimation Speed Search.
Note: When using an induction synchronous motor, the only available selection is Stationary Auto-Tuning for line-to-line resistance.
Figure 4.8
Run the motor without load; check the rotation direction and operation.
Verify external signal commands to the drive work as desired.
Run the machine and check for desired operation.
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
describes simple motor setup for V/f Control, with or without PG feedback. This procedure
From
Flowchart
A
YES
Is there a
PG encoder
on the motor?
NO
Set or verify the V/f pattern
settings E1-
.
Energy Savings
(b8-01 = 1) or
Speed Estimation Speed Search
(b3-24 = 1) enabled
when b3-01 = 1
or L2-01 = 1,2 ?
YES
Perform Rotational
Auto-Tuning for V/f Control
(T1-01 = 3)
Couple the load or machine to the motor.
Return to
Flowchart
A
Figure 4.8 Simple Motor Setup with Energy Savings or Speed Search
Set or verify the V/f pattern settings E1-
Enter the number of motor poles to E2-04 (or E4-04 for motor 2).
Set the PG speed feedback parameters (F1-
NO
Is the motor cable longer than
50 meters?
NO
Perform Stationary Auto-Tuning for
Stator Resistance (T1-01 = 2)
4.4 Start-Up Flowcharts
.
).
YES
4
83