Configuring Slave-To-Slave Communication In Step 7 - Siemens SINAMICS G120 Original Instructions Manual

Sinamics g120 inverter with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Appendix
A.7 Application examples
A.7.4

Configuring slave-to-slave communication in STEP 7

Two drives communicate via standard telegram 1 with the higher-level controller. In addition,
drive 2 receives its speed setpoint directly from drive 1 (actual speed).
Figure A-13
Setting direct data exchange in the control
Procedure
Proceed as follows to set direct data exchange in the control:
1.
2.
444
Communication with the higher-level controller and between the drives with direct data
exchange
In HW Config in drive 2 (subscriber), insert a direct
data exchange object, e.g. "Slave-to-slave, PZD2".
With a double-click, open the
dialog box to make additional
settings for the direct data
exchange.
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120dCu230p-2