Installing
4.5 Connecting inverters in compliance with EMC
EMC-compliant wiring for Power Modules with degree of protection IP20
The terminal cover is not shown in the diagram, so that it is easier to see how the cable is connected.
Figure 4-8
70
Line connection cable (unshielded) for Power Modules with integrated line filter.
If you use an external line filter, you will need a shielded cable between the line filter and the
Power Module.
Strain relief
Line supply connection
Metal mounting plate (unpainted and with a good electrical conductivity)
Motor connection
Cable shield
Cable clamps for establishing the connection between the shield and the mounting plate through
a large surface area
Motor connection cable (shielded)
Shield plate (option)
EMC-compliant wiring of a Power Module frame size E as example
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG