Technical Data, Pm240-2; High Overload - Low Overload Pm240-2 - Siemens SINAMICS G120 Original Instructions Manual

Sinamics g120 inverter with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Table 12- 28 PM240 frame sizes GX, 3 AC 380 V ... 480 V
Order No. - without filter
Values for rated load/low overload
Rated/LO power
Rated/LO input current
Rated/LO output current
Values for high overload
HO power
HO input current
HO output current
Fuse according to IEC
Fuse according to UL (from SIEMENS)
Power loss
Required cooling air flow
Cross section of line and motor cables
Tightening torque for line and motor cables
Weight
12.2.3

Technical data, PM240-2

12.2.3.1

High overload - low overload PM240-2

Permissible inverter overload
The inverters have different load capabilities, "High Overload" and "Low Overload",
depending on the expected.
Figure 12-3
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
6SL3224-...
...0XE41-3UA0
160 kW
132 kW
3NA3254
3NE1333-2
3.9 kW
360 l/s
95 ... 2 x 240 mm
3/0 ... 2 x 600 AWG
14 Nm / 120 lbf in
176 kg
Load cycles, Low Overload" and "High Overload"
12.2 Technical data, Power Modules
...0XE41-6UA0
200 kW
297 A
354 A
302 A
370 A
160 kW
245 A
297 A
250 A
302 A
3NA3260
3NE1333-2
4.4 kW
360 l/s
120 ... 2 x 240 mm
2
4/0 ... 2 x 600 AWG
14 Nm / 120 lbf in
176 kg
Technical data
...0XE42-0UA0
240 kW
442 A
477 A
200 kW
354 A
370 A
3NA3372
3NE1436-2
5.5 kW
360 l/s
185 ... 2 x 240 mm
2
2
6/0 ... 2 x 600 AWG
14 Nm / 120 lbf in
176 kg