Technical data
12.2 Technical data, Power Modules
Electrical data
Compliance with standards
Standards
CE marking
Radio interference
suppression
Approval
Ambient conditions
Ambient temperature
Relative humidity
(no condensation)
Corresponds to class
Environmental class /
harmful chemical substances
Organic/biological influences 1B1 according to
Pollution degree
Installation altitude
Mechanical strength
Vibrational load
- Displacement
- Acceleration
Shock load
- Displacement
- Acceleration
Deviations from the defined classes are shown in
Standard construction: Devices installed in the switch cabinet with EMC-conform construction, line reactor uk = 2%,
1)
shielded motor cable (e.g. Protoflex EMC) with max. 100 m cable length,
line perturbations according to EN 61000-2-4: Class 2, THD(U) total = 8% for typical line conditions (RSC > 30 ... 50);
THD(I) total: typical 30 ... 45% (15 < RSC < 50);
In transport packaging
2)
408
EN 60146-1-1, EN 61800-2, EN 61800-3, EN 61800-5-1, EN 60204-1, EN 60529, UL508C,
CSA 22.2 No. 14-13
According to EMC Directive No. 2004/108/EC and Low-Voltage Directive No. 2006/95/EC
and Machinery Directive No. 2006/42/EC
In accordance with the EMC product standard for variable-speed drives EN 61800-3,
"second environment"
.
1)
Application in "first environment" possible with line filters.
cULus (File No.: E192450), CE, c-Tick, GOST-R, KC
During storage
2)
-25 ... +55 °C
5 to 95%
1K4 according to
EN 60721-3-1
1C2 according to
EN 60721-3-1
EN 60721-3-1
2 according to EN 61800-5-1
Up to 1000 m above sea level without derating,
> 1000 m above sea level with derating (see "Derating data")
During storage
2)
Fc test according to
EN 60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g for 9 ... 200 Hz
italics
.
During transport
2)
-25 ... +70 °C
C
above –40 °
for 24 hours
5 ... 95% at 40 °C
2K3 according to
EN 60721-3-2
2C2 according to
EN 60721-3-2
2B1 according to
EN 60721-3-2
During transport
2)
Fc test according to
EN 60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g for 9 ... 200 Hz
Fc test according to
EN 60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g for 9 ... 200 Hz
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
During operation
0 ... +40 °C
up to +50 °C with derating
5 ... 95%
3K3 according to
EN 60721-3-3
3C2 according to
EN 60721-3-3
3B1 according to
EN 60721-3-3
During operation
Fc test according to
EN 60068-2-6
0.075 mm for 10 ... 58 Hz
9.81 ma/s² (1 x g) for
> 58 ... 200 Hz
Test according to EN 60068-
2-27 (EA shock type)
49 ma/s² (5 x g)/30 ms
147 ma/² (15 x g)/11 ms