Setting functions
8.7 Application-specific functions
Restrictions for the unit changeover function
● The values on the rating plate of the inverter or motor cannot be displayed as percentage
values.
● Using the unit changeover function several times (for example, percent → physical unit 1
→ physical unit 2 → percent) may lead to the original value being changed by one decimal
place as a result of rounding errors.
● If the unit is changed over into percent and the reference value is then changed, the
percentage values relate to the new reference value.
Example:
– For a reference speed of 1500 rpm, a fixed speed of 80% corresponds to a speed of
– If the reference speed is changed to 3000 rpm, then the value of 80% is kept and now
Reference variables for unit changeover
p2000
p2001
p2002
p2003
r2004
p2005
p2006
8.7.1.1

Changing over the motor standard

You change over the motor standard using p0100. The following applies:
● p0100 = 0: IEC motor (50 Hz, SI units)
● p0100 = 1: NEMA motor (60 Hz, US units)
● p0100 = 2: NEMA motor (60 Hz, SI units)
The parameters listed below are affected by the changeover.
Table 8- 24
P no.
r0206
p0307
p0316
r0333
r0334
p0341
p0344
r1969
*) Factory setting
268
1200 rpm.
means 2400 rpm.
Reference frequency/speed
Reference voltage
Reference current
Reference torque
Reference power
Reference angle
Reference temperature
Variables affected by changing over the motor standard
Designation
Power Module rated power
Rated motor power
Motor torque constant
Rated motor torque
Motor torque constant, actual
Motor moment of inertia
Motor weight (for thermal motor type)
Speed_cont_opt moment of inertia determined
0*
)
kW
kW
Nm/A
Nm
Nm/A
kgm
2
kg
kgm
2
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Unit for p0100 =
1
2
HP
kW
HP
kW
lbf ft/A
Nm/A
lbf ft
Nm
lbf ft/A
Nm/A
lb ft
kgm
2
2
Lb
kg
lb ft
kgm
2
2

Advertisement