You have commissioned the automatic restart function.
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
The inverter automatically acknowledges faults under the following conditions:
1
p1210 = 1 or 26: Always.
p1210 = 4 or 6: If the command to switch-on the motor is available at a digital input or via the
fieldbus (ON/OFF1 = 1).
p1210 = 14 or 16: Never.
The inverter attempts to automatically switch-on the motor under the following conditions:
2
p1210 = 1: Never.
p1210 = 4, 6, 14, 16, or 26: If the command to switch-on the motor is available at a digital
input or via the fieldbus (ON/OFF1 = 1).
If no fault has occurred one second after flying restart and magnetizing (r0056.4 = 1), the start
3
attempt was successful.
Figure 8-26
Time response of the automatic restart