Siemens SINAMICS G120 Original Instructions Manual page 122

Sinamics g120 inverter with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Configuring the fieldbus
7.3 PROFIdrive profile for PROFIBUS and PROFINET
Status word 3 (ZSW3)
Status word 3 has the following standard assignment.
Bit Value Significance
0
1
DC braking active
1
1
|n_act| > p1226
2
1
|n_act| > p1080
3
1
i_act ≧ p2170
4
1
|n_act| > p2155
5
1
|n_act| ≦ p2155
6
1
|n_act| ≧ r1119
7
1
DC link voltage ≦ p2172
8
1
DC link voltage > p2172
9
1
Ramping completed
10 1
Technology controller output at lower
limit
11 1
Technology controller output at upper
limit
12
Not used
13
Not used
14
Not used
15
Not used
122
Description
--
Absolute current speed > stationary state
detection
Absolute actual speed > minimum speed
Actual current ≥ current threshold value
Absolute actual speed > speed threshold
value 2
Absolute actual speed < speed threshold
value 2
Speed setpoint reached
Actual DC link voltage ≦ threshold value
Actual DC link voltage > threshold value
Ramp-function generator is not active.
Technology controller output ≦ p2292
Technology controller output > p2291
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Signal interconnection
in the inverter
p2051[3] = r0053
Inverter with CU230P-2 Control Units