FP2 Analog Unit
6.2
Analog Output Conversion Characteristics
The conversion characteristics of analog output range are shown below.
10V to +10V DC
-
- 2048
- 1024
Output range - 10V to +10V DC
V
K
- 10
- 2048
- 7.5
- 1536
- 5
- 1024
- 2.5
- 512
0
0
2.5
511
5
1023
7.5
1534
10
2047
If the input value exceeds the rated digital input range, the analog output value becomes:
Digital input value
- 2049 or less
+2048 or more
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Analog I/O Conversion Characteristics and Conversion Cycle Time
(V)
+10
+5
0
+1023
+2047
- 5
- 10
Analog output value
Invariable (holds the output value that corresponds to the previous effective
input value)
Invariable (holds the output value that corresponds to the previous effective
input value)
6.2
Analog Output Conversion Characteristics
(K)
6 - 11