Panasonic FP2 -C1A Manual page 56

Analog unit
Table of Contents

Advertisement

Analog I/O Conversion Characteristics and Conversion Cycle Time
6.3
Analog Input and Output Conversion Cycle Time
Example of conversion cycle time calculation 2
Ch0 thermocouple K
Ch1 thermocouple J
Ch2
10V
±
Ch3 thermocouple J
Ch4 not used
Ch5 not used
Ch6 thermocouple J
Ch7 not used
Ch2 (
10V) conversion cycle time = (0.5
±
Ch0 (thermocouple K) conversion cycle time = (0.5
The conversion cycle time when setting the range for each analog input channel was
explained above; however, the conversion cycle time when the ranges for all channels
are set together by the DIP switches can be determined by the formula below.
Conversion cycle time = set range conversion speed
6.3.2
Analog Output Conversion Cycle Time
The analog output conversion cycle time can be determined by the formula below.
Conversion cycle time = conversion speed (0.5ms)
6 - 14
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Number of input channels used: n1 = 5
Number of gain types: n2 = 2
Number of temperature input channels: n3 = 4
5 + 2
2 + 3
×
×
×
5 + 2
×
number of input channels used
×
(number of input channels set
for execution of conversion
processing)
number of output channels used
×
(number of output channels set
for execution of conversion
processing)
FP2 Analog Unit
4)
1 = 18.5ms
×
2 + 3
4)
30 = 555ms
×
×
×