Panasonic FP2 -C1A Manual page 47

Analog unit
Table of Contents

Advertisement

FP2 Analog Unit
1V to 5V DC
(K)
+13107
+6553
0
+1
Input range 1V to 5V DC
V
K
1
0
2
3276
3
6553
4
9829
5
13107
If the input value exceeds the rated analog input range, the converted value becomes:
Input value
1V or less
5V or more
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Analog I/O Conversion Characteristics and Conversion Cycle Time
+3
+5
Converted value
0
+13107
6.1
Analog Input Conversion Characteristics
(V)
6 - 5