Shared Memory For Analog Input Processing - Panasonic FP2 -C1A Manual

Analog unit
Table of Contents

Advertisement

FP2 Analog Unit

14.4 Shared Memory for Analog Input Processing

14.4.1
Analog Input Preparation Completion Flag (address 10)
After the power is turned on and the first conversion is completed, the input channel
where the conversion data preparation is completed is copied to the bits shown below.
15
14
Bit position
Address 10
14.4.2
No Execution of Analog Input Conversion Processing Setting
(address 16 and 17)
Specifies the input channel where conversion processing is not executed.
15
14
Bit position
Address 16
15
14
Bit position
Address 17
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
13
12
11
10
13
12
11
10
ch 3
13
12
11
10
ch 7
14.4 Shared Memory for Analog Input Processing
9
8
7
6
5
ch 7 ch 6 ch 5 ch 4 ch 3 ch 2 ch 1 ch 0
9
8
7
6
5
ch 2
0: Conversion not executed
1: Conversion executed
(Deffault: H1111)
9
8
7
6
5
ch 6
0: Conversion not executed
1: Conversion executed
(Deffault: H1111)
Specifications
4
3
2
1
0: Preparing
1: Preparation completed
(Default: H0000)
4
3
2
1
ch 1
ch 0
4
3
2
1
ch 5
ch 4
14 - 13
0
0
0