Panasonic FP2 -C1A Manual page 108

Analog unit
Table of Contents

Advertisement

Specifications
14.1
Table of Performance Specifications
14.1.3
Analog Output Specifications
Item
Number of output points
Output range
p
g
Voltage
(digital input)
Current
Resolution
Conversion speed
Overall accuracy
Output impedance
Maximum output current
Allowable output load resistance Current output: Max. 300Ω
Insulation method
Analog output hold setting
Notes
1) For the FP2 analog output unit (FP2 - DA4), there are
restrictions regarding the ambient temperature that depend on
how many channels are used. Use according to the restrictions
listed in "Ambient temperature"of "section 14.1.1 General
Specifications."
2) For information regarding the conversion cycle time when
using multiple channels, refer to "section 6.2 Analog I/O
Conversion Cycle Time."
14 - 6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Specifications
1 channel (FP2 - C1A), 4 channels (FP2 - DA4) (* Note 1)
±10V (K - 2048 to K+2047)
0 to 20mA (K0 to K4095)
1/4096
500µs/channel (* Note 2)
Max. ±1.0% F.S. (0 to 55_C/32 to 131_F)
Voltage output: Max. 0.5Ω
Voltage output: 10mA (FP2 - C1A), 5mA (FP2 - DA4)
S Between analog output terminal and FP2 internal circuits: Optical coupler
insulation
S Between analog output channels: Non insulation (for FP2 - DA4)
S Between analog output terminal and analog input terminal: DC/DC converter
insulation (for FP2 - C1A)
Hold/non hold setting by shared memory setting
FP2 Analog Unit