Panasonic FP2 -C1A Manual page 118

Analog unit
Table of Contents

Advertisement

Specifications
14.4
Shared Memory for Analog Input Processing
14.4.5
Offset Changing Setting (address 30 to 37)
Sets the offset data for each channel that executes offset changing (range: - 2048 to
+2047).
15
14
Bit position
Address 30
to
Address 37
Address 30:
Analog input ch 0
Address 31:
Analog input ch 1
Address 32:
Analog input ch 2
Address 33:
Analog input ch 3
Address 34:
Analog input ch 4
Address 35:
Analog input ch 5
Address 36:
Analog input ch 6
Address 37:
Analog input ch 7
14.4.6
Input Sensor (TC, R.T.D.) Broken Wire Detection Flag (address 42)
Detects broken wires in the input wiring onlly for each input channel tha is set for the
thermocouple input range or R.T.D. (resistance thermometer device) input range, and
copies the data to the bits shown below.
15
14
Bit position
Address 42
14 - 16
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
13
12
11
10
9
13
12
11
10
9
8
7
6
5
K- 2048 to K2047
(Default: K0)
8
7
6
5
ch 7 ch 6 ch 5 ch 4 ch 3 ch 2 ch 1 ch 0
0: Normal
FP2 Analog Unit
4
3
2
1
4
3
2
1
1: Broken wire detected
0
0