Safety Validation and Preparations for Operation

10-4 Safety Validation and Preparations for Operation

10-4-1 Performing Safety Validation Testing (User Testing)

!WARNING

10-4-2 Backing Up Data to the Memory Cassette

10-4-3 Outputting and Saving Reports

158
The following operations are performed after checking G9SP-series Controller
operation and completing debugging and before starting actual operation.
1. Performing safety validation testing (user testing)
2. Backing up data to the Memory Cassette
3. Printing and saving a report
Safety validation testing is performed to confirm that all of the Safety Func-
tions of the entire system containing the G9SP-series Controller are operating
correctly. After completing safety validation testing, the configuration is locked
to protect it from unintentional changes.
Additional Information
Locking the configuration enables automatic operation of the G9SP-series
Controller in RUN Mode. Refer to 9-3 Configuration Lock and Automatic Oper-
ation for details.
Serious injury may possibly occur due to loss of required safety functions.
Perform user testing and confirm that all of the G9SP-series Controller's con-
figuration data and operation is correct before starting system operation.
After the configuration data is locked, it is backed up to a Memory Cassette.
Refer to SECTION 11 Backup and Restore Data Using Memory Cassette for
Memory Cassette functions, details, and procedures.
Additional Information
• Memory Cassettes can be used to greatly reduce the work required in
replacing a G9SP-series Controller. We recommend that you use Memory
Cassettes.
• Configuration data must be locked before it can be backed up to a Memory
Cassette.
After the configuration data has been completed, it can be checked in a
report, which can be printed or saved as required. Refer to 6-2-5 Displaying
and Printing Reports for the procedures.