System Options 3 - Bosch Solution 2000 Installation Manual

Hide thumbs Also See for Solution 2000:
Table of Contents

Advertisement

Control Panel
18.2
System Options 2
Item
System Options 2
1 – Codepad Panic to Be Silent
If this option is selected, a Codepad Panic Alarm or Radio Remote Panic Alarm does not
operate the horn speaker, the bell, or the strobe outputs. If this option is not selected, all
three outputs operate after a Codepad Panic Alarm is activated when a user presses [1] and
[3] or [STAY] and [AWAY] at the same time on the remote codepad. Selecting this option does
not affect the operation of the communication report.
2 – Codepad Fire to Be Silent
If this option is selected, a Codepad Fire Alarm does not operate the horn speaker, the bell, or
the strobe outputs. If this option is not selected, all three outputs operate after a Codepad
Fire Alarm is activated when a user presses [4] and [6] at the same time on the remote
codepad. Selecting this option does not affect the operation of the communication report.
4 – Codepad Medical to Be Silent
If this option is selected, a Codepad Medical Alarm does not operate the horn speaker, the
bell, or the strobe outputs. If this option is not selected, all three outputs operate after a
Codepad Medical Alarm is activated when a user presses [7] and [9] at the same time on the
remote codepad. Selecting this option does not affect the operation of the communication
report.
8 – Access Denied (Code Retries) to Be Silent
If this option is selected, a Codepad PIN Error Alarm does not operate the horn speaker, bell,
or the strobe outputs. If this option is not selected, all three outputs operate after a Codepad
PIN Error Alarm occurs. Selecting this option does not affect the operation of the
communication report. If you want to disable the reporting of Access Denied reports, program
Locations 424 as 0.
18.3

System Options 3

Item
System Options 3
1 – AC Fail after 1 Hour
If this option is selected, the MAINS indicator flashes when the AC MAINS supply is
disconnected. An AC Loss signal (Contact ID Event Code 301) is transmitted to the base
station receiver after the AC MAINS supply is disconnected continuously for longer than 60
min.
If this option is not selected, the MAINS indicator flashes and an AC Loss signal (Contact ID
Event Code 301) is transmitted to the base station receiver after the AC MAINS power is
disconnected continuously for 2 min.
Bosch Security Systems, Inc.
Location
Option
0493
1 = Codepad panic to be silent
2 = Codepad fire to be silent
4 = Codepad medical to be silent
8 = Access denied (code retries) to be silent
Location
Option
0494
1 = AC fail after 1 hr. (Disabled = after 2 min.)
2 = Ignore AC fail
4 = Pulse count handover allowed
8 = Handover delay to be sequential
Installation Guide
System and Consumer Options | en
Default
New
0
Default
New
8
2017.10 | 03 | F.01U.298.026
139

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Solution 3000

Table of Contents