Sensor Watch Report; Alarm Restore Code; Rf Receiver Trouble Report; Rf Receiver Trouble Restore Report - Bosch Solution 2000 Installation Manual

Hide thumbs Also See for Solution 2000:
Table of Contents

Advertisement

114
en | System Reporting Information
A 24-Hour Duress Zone Trouble is reported as Contact ID Event Code 376.
A 24-Hour Fire Zone Trouble is reported as Contact ID Event Code 373.
15.7.5

Sensor Watch Report

A Self Test Failure Report (Contact ID Event Code 391) is sent to the base station receiver
when a zone was not activated during the Sensor Watch Time programmed in Locations 476
and 477.
To clear the fault, you must unseal and reseal the zone that registered the fault. Use the
Sensor Watch Time in Locations476 and 477 to set the number of days a zone can remain
sealed without registering a fault. Refer to Zone Options 1, page 100 to program the zone as
Sensor Watch.
15.7.6

Alarm Restore Code

A Zone Restore Report is sent only to the receiving party to which the zone is allocated (for
example, Receiver 1 or Receiver 2). Refer to Zone Options 2, page 101 for Zone Restore
Report.
15.7.7

RF Receiver Trouble Report

RF Signal Jamming (Contact ID Event Code 344, Point ID Code 821)
RF Receiver Tamper Switch (Contact ID Event Code 341, Point ID Code 821)
RF Receiver Missing (Contact ID Event Code 333, Point ID Code 821)
15.7.8

RF Receiver Trouble Restore Report

An RF Receiver Trouble Restore Report is sent to the base station receiver when the RF
receiver no longer registers RF Signal Jamming, RF Receiver Tamper Switch, or RF Receiver
Missing.
15.7.9

RF Low Battery Report

An RF Low Battery Report (Contact ID Event Code 384) is sent to the base station receiver
when the battery voltage on a wireless zone falls below its corresponding low battery
condition. An RF Low Battery Restore Report is sent on the first valid signal after the battery is
replaced.
15.7.10

Arm/Disarm Reports

A Disarm Report (Contact ID Event Code 401) is sent to the base station receiver when the
system is disarmed from AWAY Mode or STAY Mode. An Arm Report (Contact ID Event Code
401 for arming in AWAY Mode, Contact ID Event Code 441 for STAY Mode 1, Contact ID Event
Code 456 for STAY Mode 2) is sent at the end of Exit Time when the system is armed.
The user number that armed or disarmed the system follows in the same transmission.
For a keyswitch zone, its zone number is reported as a user code number.
User Code for single button arming/disarming : 00.
User Code for arm tracking on Power Up : 994.
User Code for arming remotely by telephone : 995.
User Code for automatic arming/disarming : 997
User Code for arming and disarming using the A-Link Plus software / RSC : 998.
To enable Arm/Disarm Reports in STAY Mode: Select Option 2 in Location 178.
To enable Arm/Disarm Reports only after a previous alarm, select Option 1 in Location 178
(refer to Communication Options 2, page 77.
2017.10 | 03 | F.01U.298.026
Installation Guide
Control Panel
Bosch Security Systems, Inc.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Solution 3000

Table of Contents