Control Panel
2 – User Code Allowed to Arm/Disarm Both Areas at the Same Time
If this option is selected, any user allocated to both areas can arm or disarm both areas at the
same time without entering the code at each area codepad.
If the user arms both areas at the same time and Option 1 is selected in Location 500, only an
Arm Report for Area 2 is sent.
If the user disarms both areas at the same time and Option 1 is selected in Location 500, only
a Disarm Report for Area 1 is sent.
See also
19.2
Partition Allocations
You can allocate up to 16 zones to each zone for the control panel. The 16 locations for each
area are represented by the zone indicators on the ICON codepad. You can assign any zone to
either area or both Area 1 and Area 2 to become a common zone.
Zones programmed as common zones report to the base station receiver on group zero (Area
1 – Group 1 and Area 2 – Group 2). Zones allocated to only one area report on the
corresponding group number. Common zones, other than 24-Hour zone types, do not activate
an alarm until both areas are armed in either AWAY Mode or STAY Mode 1.
Zone, user code, and codepad should be assigned to the correct area to operate. If a user
code is assigned to an area only, the user code can only operate the assigned area on this
area's codepad. For user code and authority level, refer to User Code Priority, page 89.
Example:
Two methods to arm/disarm both areas at the same time:
Two methods to arm/disarm single area:
19.2.1
Zone Area Assignments
Item
Location
Zone 1 Area
0502
Zone 3 Area
0504
Zone 5 Area
0506
Zone 7 Area
0508
Zone 9 Area
0510
Bosch Security Systems, Inc.
Arm or Disarm both Areas at the Same Time, page 51
[User Code] + [0][# / *]: this method requires to allocate the same user code to both
areas as a common user code, then you can arm/disarm both areas at the same time with
any area codepad. Refer to Arm or Disarm both Areas at the Same Time, page 51 for more
information.
[User Code] + [# / *]: this method requires to allocate the same user code to both areas
as a common user code, and allocate the same codepad to both areas as a common
codepad, then you can arm/disarm both areas at the same time with the common user
code and common codepad.
[User Code] + [01] / [02] + [# / *]: this method requires to allocate the same user code to
both areas as a common user code, and you can are/disarm any single area with any
codepad.
[User Code] + [# / *]: this methods requires to allocate the user code and codepad to
either area, you can only arm/disarm the single area with corresponding user code and
codepad.
Default
New
1
1
1
1
1
Item
Location
Zone 2 Area
0503
Zone 4 Area
0505
Zone 6 Area
0507
Zone 8 Area
0509
Zone 10 Area
0511
Installation Guide
Partitioning | en
Default
New
1
1
1
1
1
2017.10 | 03 | F.01U.298.026
145