Alarm Signal Response; System Operation (Main Menu Options); System Tests; Leds Test - Bosch Radionics D8024 Operator's Manual

Analog fire alarm control panel
Hide thumbs Also See for Radionics D8024:
Table of Contents

Advertisement

4.3.2

Alarm Signal Response

Press the [Alarm Silence] key to turn off all external NAC devices. The Alarm Silenced LED will light. Pressing the
[Alarm Silence] key again turns on all external NAC devices.
Press the [Trouble Silence] key to turn the panel buzzer off. The amber Trouble Silenced LED will light.
Press the [System Reset] key to reset the system. The Alarm and Trouble Silenced LEDs will go out and the alphanumeric
display will return to normal.
Note:
The D8024 can be reset at any time, however if a device is still in alarm when the D8024 is reset, the D8024 will go back
into an alarm condition.
To return the system to Control Level 1, press the [Shift] key and select 5) Disable from the alphanumeric display. Then
select 3) Keys from the display. The panel will briefly display the Control Level 2 Entry Menu 2 and then revert to the
normal display (alternating between a time and date display and a system status message). Press the [Fire Drill] key
to verify that the keys are disabled.
4.4

System Operation (Main Menu Options)

Pressing the [Shift] key from the normal display will open the Main Menu on the alphanumeric display. The first option,
1) Commission, is not available to Control Level 2 Operators. See the Analog Fire Alarm Control Panels Programming
Guide (P/N: 38789) for commissioning and programming information. The other options on the Main Menu permit tests
and the setting, enabling and disabling of various system functions.
4.4.1

System Tests

Select 2) Test from the Main Menu to open the Test Menu. This menu allows the Control Level 2 user to test the following:
• The LEDs on the Front Panel Display
• The alphanumeric (liquid crystal) display
• Detection and alarm initiating devices connected to the polling circuit
• NAC and other alarm condition devices connected to the system
If no action is taken, the display reverts to the normal display after one minute.

4.4.1.1 LEDs Test

Select the first option, 1) LEDs, by pressing the [1] key. The panel will flash all LEDs on the LED display and step
through all the alarm and trouble LEDs in the Zone/Area display. On completion of the test, press [No] to return the
display to the Main Menu.

4.4.1.2 LCD Test

Select the second option, 2) LCD, from the Main Menu by pressing the [2] key. The alphanumeric display will flash all
characters in all spaces on the alphanumeric display and return to the Main Menu.
Copyright © 2001 Radionics
[ACTIVE]
1) Commission 2) Test 3) Time
4) Enable 5) Disable 6) Print 7) View

Figure 9: Main Menu

1) LEDs
2) LCD

Figure 10: Test Menu

D8024 Operator's Guide
Page 15
National Security Systems (800)457-1999
http://www.nationalsecuritysystems.com
[1]
3) Zones
4) Outputs
D8024
Control Level 2
35394D