124
en | Programmable Outputs
Control Panel
This output operates during the time period before the control panel is automatically armed in
AWAY Mode or STAY Mode 1. The output is reset when the control panel is automatically
armed in AWAY Mode or STAY Mode 1. The Auto Arming Pre-Alert Time is programmed in
Location 481.
0,6 Exit Warning with All Zones Sealed or Entry Warning
This output operates during Exit Time when the control panel is armed and all zones are
sealed. The output is reset when Exit Time expires.
This output operates again during Entry Time and is reset when Entry Time expires or the
system is disarmed.
This output also operates if a zone is activated when the system is armed in STAY Mode 1 or
STAY Mode 2 and the Entry Guard Timer for STAY Mode is programmed in Locations 472 and
473.
0,7 Exit Warning
This output operates during Exit Time when the system is armed. The output is reset when
Exit Time expires or the system is disarmed.
0,8 Exit Warning Finished
This output operates after Exit Time expires when the system is armed. The output is reset
when the system is disarmed.
0,9 Kiss-Off after Exit Time
This output operates after the first successful transmission to the base station receiver when
Exit Time expires. The output is reset when the system is disarmed.
0,11 Entry Warning
This output operates when during Entry Timer 1, Entry Timer 2, or Entry Guard Timer for STAY
Mode. The output is reset when the Entry Time or Entry Guard Time expires or the system is
disarmed. If Entry Time and Entry Guard time are present together, the output will follow the
Entry Guard Time.
0,12 Entry Warning + Day Alarm Resetting
This output combines Entry Warning and Day Alarm Resetting so that either of these two
events activates the output.
If the output is activated by Entry Timer 1, Entry Timer 2, or Entry Guard Timer for STAY Mode,
the output is reset when the Entry Time or Entry Guard Time expires or the system is
disarmed.
If a zone programmed for Day Alarm is activated when the system is disarmed and Day Alarm
is turned on in the area to which this zone is allocated, the output is reset when the zone is
resealed or Day Alarm is turned off in the area to which this zone is allocated or the system is
armed. You can turn Day Alarm on and off by holding down [4] or selected from the menu on
KP.
0,13 Exit Warning + Entry Warning + Day Alarm Resetting
This output operates when the system is armed, regardless of whether zones are sealed or
unsealed, until Exit Time expires or the system is disarmed.
The output operates again during Entry Time and is reset when Entry Time expires or the
system is disarmed. The output also operates during the Entry Guard Timer for STAY Mode
time and is reset when the Entry Guard Time expires or the system is disarmed.
If a zone programmed for day alarm is activated when the system is disarmed or Day Alarm is
turned off in the area to which this zone is allocated or the system is armed, the output is
reset when the zone is resealed or Day Alarm is turned off in the area to which this zone is
allocated or the system is armed. You can turn Day Alarm on and off by holding down [4] or
selected from the menu on KP.
0,14 Day Alarm Resetting
2017.10 | 03 | F.01U.298.026
Installation Guide