Serial Communication Error Code [D8062, D8063 And D8438] - Mitsubishi Electric FX3U-232-BD User Manual

Melsec-f fx series programmable controllers data communication edition
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
Non-Protocol Communication (RS/RS2 Instruction)

12.4.8 Serial communication error code [D8062, D8063 and D8438]

When a serial communication error occurs, these devices store the corresponding error codes.
1. Detailed contents
When a serial communication error occurs, these devices store the corresponding error codes shown below.
When communication port ch0 is used, M8062 turns ON.
When communication port ch1 is used, M8063 turns ON.
When communication port ch2 is used, M8438 turns ON.
ch0 (D8062)
6201
6202
6203
6204
6205
6206
2. Cautions on use
Serial communication error codes are not cleared even when communication is restored.
Cleared when the power is turned off and on.
F-100
Error code
ch1 (D8063)
ch2 (D8438)
6301
3801
6302
3802
6303
3803
6304
3804
6305
3805
6306
3806
6307
3807
6308
3808
6309
3809
6312
3812
6313
3813
6314
3814
6320
3820
6321
3821
6330
3830
6340
3840
Contents of error
Parity error, overrun error or framing error
Incorrect communication character
Communication data sum mismatch
Incorrect data format
Incorrect command
Monitoring timeout
Modem initialization error
N:N Network parameter error
N:N Network setting error
Parallel link parameter error
Parallel link sum error
Parallel link format error
Inverter communication error
MODBUS communication error
Memory access error
Special adapter connection error