Details Of Related Devices - Mitsubishi Electric FX3U-232-BD User Manual

Melsec-f fx series programmable controllers data communication edition
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
N:N Network
10.2

Details of Related Devices

The devices described below are used in the N:N Network.
10.2.1 Parameter setting [M8038]
This device works as the communication parameter setting flag.
1. Stations requiring program setting
Setting is required for the master station and slave stations.
2. Detailed contents
"LD M8038" provided in step 0 starts the parameter setting, and the last instruction in this circuit block finishes
the setting.
(This sequence program is not executed in every scan cycle.)
3. Cautions on use
Do not set this device to ON using a program or programming tool.
10.2.2 Channel setting [M8179]
This device works as the channel setting flag (in the FX
1. Stations requiring program setting
Setting is required for the master station and slave stations.
2. Detailed contents
When using ch 2 as the communication port, set this device to ON in the sequence program.
When using ch 1, the sequence program is not required.
10.2.3 Serial communication error [M8063 and M8438]
These devices turn ON when an error is included in the parameters used to set the N:N Network. (M8438 is
available in the FX
1. Stations requiring program setting
Setting is required for the master station and slave stations to check the communication status.
2. Detailed contents
M8063 turns ON when an error is included in the parameters used to set N:N Network using ch 1.
M8438 turns ON when an error is included in the parameters used to set N:N Network using ch 2.
3. Cautions on use
Do not set these devices to ON using a program or programming tool.
Serial communication errors are not cleared even when communication is restored.
Serial communication errors are cleared in FX
turned off and on.
Serial communication errors are cleared in other PLCs when the mode is switched from STOP to RUN.
B-60
, FX
, FX
and FX
3G
3GC
3U
, FX
, FX
3G
3GC
.)
3UC
, FX
, FX
, FX
3S
3G
3GC
10.2 Details of Related Devices
and FX
).
3U
3UC
and FX
PLCs when the power is
3U
3UC
10 Related Data