Mitsubishi Electric FX3U-232-BD User Manual page 620

Melsec-f fx series programmable controllers data communication edition
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
Non-Protocol Communication (RS/RS2 Instruction)
5. Cautions on receiving
When receiving data, observe the following cautions
1) While the receiving complete flag is ON, the PLC cannot receive the next set of receive data.
When the receiving complete flag is set to OFF, the PLC waits to receive.
2) If the RS2 instruction is driven while the amount of received data "n" is "0", the receiving complete flag
(M8373, M8403, M8423) turns ON. To make the PLC wait to receive, set the amount of received data "n"
to "1" or more, and set the receiving complete flag (M8373, M8403, M8423) to OFF from ON.
3) Set the amount of received data to a value including "terminators", "sum check" and "CR+LF".
If the specified amount of received data is small, the serial communication error flag (M8062, M8063 or
M8438) turns ON.
F-70
8 Creating Programs (RS2 Instruction)
8.2 How to Use RS2 Instruction