FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
4
Setting the set value of "n2" to "192"
("192" indicates the baud rate of 19200 bps.)
Turn the setting dial to display "n2".
Press the SET key to read the currently set value.
Turn the setting dial to change the set value to "192".
Press the SET key to set "192".
When the set value and parameter number are displayed alternately, the setting is completed.
5
Changing other parameters in the same way as step 4
E-52
The set value and parameter number are displayed alternately.
For details on the parameters to be set, refer to Subsection 5.2.1.
5 Communication Setting in Inverter
5.2 S500 Series (When Connected to RS-485 Port)