Checking Absence/Presence of Errors

Verify that errors have not occurred in the master station and slave station. Errors can be checked using the
flags shown below.
1. Checking the device M8072
While the parallel link is established, M8072 remains ON.
If M8072 is OFF, an error has occurred in the parallel link setting or communication.
2. Checking the device M8073
If the parallel link is not set correctly, M8073 turns ON.
If M8073 is ON, verify that the master station and slave station are set correctly in sequence programs.
3. Devices for checking link errors
1) Checking the error flags M8063 and M8438 (in the FX
If a communication error occurs in the parallel link, the serial communication error flag turns ON.
When ch1 is used, M8063 turns ON. When ch2 is used in the FX
turns ON.
When the serial communication error flag turns ON, the error code is stored in D8063 or D8438.
2) Checking the error code
When a communication error occurs in parallel link using ch 1, the error code is stored in D8063.
When a communication error occurs in parallel link using ch 2, the error code is stored in D8438.
The table below shows the details of error codes.
Device
D8063
D8438
(in FX
, FX
3G
3GC
FX
3UC
Caution
The devices for checking link errors are not cleared even after communication errors are reset.
Serial communication errors are cleared in FX
turned off and on.
Serial communication errors are cleared in other PLCs when the mode is switched from STOP to RUN.
Error code
0000
No error
6312
Character error in parallel link
6313
Sum check error in parallel link
6314
Format error in parallel link
0000
No error
3812
Character error in parallel link
,
FX
and
3U
3813
Sum check error in parallel link
)
3814
Format error in parallel link
3S
9.5 Checking Absence/Presence of Errors
, FX
, FX
3G
3GC
3U
, FX
3G
Description
, FX
, FX
, FX
and FX
3G
3GC
3U
9 Troubleshooting
and FX
)
3UC
, FX
and FX
, M8438
3GC
3U
3UC
Action
Verify that the parallel link
setting programs are set
correctly. Check the wiring
also.
PLCs when the power is
3UC
C-51
A
B
C
D
E
F
G
H
I
Apx.A