Cautions on programming

1. Using an inverter communication instruction together with another instruction
• An inverter communication instruction using ch1 cannot be used together with a RS instruction.
• An inverter communication instruction cannot be used together with a RS2 instruction if the RS2 instruction
uses the same channel.
2. When programming an inverter communication instruction in a state of a STL instruction
Make sure to let the state relay remain ON until communication with an inverter is completed. Program a
sequence while observing the following cautions
• Add M8029 (instruction execution complete flag) ON condition to the state relay transfer condition, and
provide such interlock that the state relay ON/OFF status does not change during communication with an
inverter.
If the state changes during communication, communication may not be performed normally.
• When resetting many state relays all at once using the ZRST (FNC 40) instruction, etc., make sure that the
M8151 or M8156 (communication port busy) condition is OFF.
X000
Reset input
M0
3. Using an inverter communication instruction in a program flow
An inverter communication instruction cannot be used in the following program flows
Program flow disabling the inverter communication
Between FOR and NEXT instructions
4. Caution on writing during RUN
1) Condition in which inverter communication instruction can be written:
While the PLC is in the STOP status, inverter communication instruction can be written during RUN.
2) Condition in which inverter communication instruction cannot be written:
Inverter communication instruction cannot be written during RUN.
If an inverter communication instruction is written during RUN during communication or if an inverter
communication instruction is deleted while in RUN, communication may be disabled after that. (In such a
case, set the PLC to STOP, and then to RUN mode again to initialize the status.)
5. When using the E500 Series
Parameters Nos. 922 and 923 in the E500 Series cannot be used in inverter communication.
E-102
M8151
FNC 40
ZRST
Communication
port busy
instruction
Between CJ and P instructions
Between P and SRET instructions
Between I and IRET instructions
9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
9.3 Common Items in Inverter Communication Instructions
SET
M0
State relays S0 to S999
S0
S999
are reset all at once.
RST
M0
Conditional jump
Repeat
Subroutine
Interrupt routine
Remarks

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents