Mitsubishi Electric FX3U-232-BD User Manual page 414

Melsec-f fx series programmable controllers data communication edition
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
3
Setting the serial communication (parameters)
Set the parameters as shown below:
[1]
[2]
[3]
[4]
[1] Set the channel to be used. (This parameter can be set only in the FX
FX
PLCs.)
3UC
[2] Check the "Operate Communication Setting" box.
[3] Set "Protocol" to "Non-procedural", "Data Length" to "7Bit", "Parity" to "Even", and "Stop Bit" to
"1Bit".
[4] Set "Transmission Speed" to either "4800", "9600", "19200" or "38400
the set value here is the same as the set value in the inverters.
[5] Ignore these items.
*1.
This transmission speed is supported only in FX
Click [End].
4
Writing parameters and program to the PLC
Select [Online]  [Write to PLC] from the menu bar, click [Parameter + Program], and then click
[Execute].
E-72
6 Communication Setting in FX Programmable Controller
6.2 Communication Setting Using Parameter Method (GX Works2)
[5]
, FX
, FX
, FX
and FX
3S
3G
3GC
3U
FX
, FX
and
,
3G
3GC
3U
*1
", and make sure that
PLC
.
3UC
S