Battery Test Printout (Ctrl + B)

This key sequence prints the Battery Test Log. The log consists of a history of the
last 30 battery tests that were run and the results of those tests. The most recent
test will appear at the bottom of the log. Figure 29 shows a sample of the Battery
Test Log.
Uninterruptible Power System
UPS System Normal
Alarm:
Notice:
Date/Time
AUG
SEP
OCT
NOV
DEC
JAN
FEB
MAR
APR
The Date/Time field is the date and time of the battery test.
The Volts field is a measured value of the battery voltage during the test. This field
will display 000.0 if the test did not run to completion.
The Health field is a relative measurement of your batteries condition. This number
can be used to chart the condition of your batteries. If a sudden change of this
number occurs relative to the previous test results, it is an indication that your
batteries may need attention. This display is 0.00 if the test does not run to
completion.
The Data field is a value to be used by your field service engineer to gain more
information about the battery tests.
If the battery test does not complete, the Volts and Health field will read zero and
the UPS Event History Log will report either Battery Test Failed, Battery Test
Aborted (Load), or Battery Test Aborted (Utility). If the test ran to completion,
Battery Passed Test will appear in the UPS Event History Log.
Powerware 9315 (200 kVA ---300 kVA) Operation

164201036 Rev. D 041500

UPS # 1
None
None
Battery Test Log
Volts
Health
14 23:45 498.0 1.00
11 23:45 498.0 1.00
9
23:45 498.0 1.00
13 23:45 498.0 0.99
11 23:45 498.0 0.99
8
23:45 498.0 0.98
12 23:45 498.0 0.98
12 23:41 000.0 0.00
9
23:45 496.2 0.98

Figure 29. Battery Test Log

12 APR 97
Data
0000
0000
0000
0000
0000
0000
0000
0003
0000
15:39:31
49