System Output - Powerware 9315 Operation Manual

200 kva -- 300 kva
Hide thumbs Also See for 9315:
Table of Contents

Advertisement

System Output

Rectifier/Charger Capacity
DC Filtering
UPS Output Capacity
Output Voltage Regulation
Output Voltage Adjustment
(Nominal +/-- 5%)
Output Voltage Harmonic Content
Output Voltage Balance
Output Voltage Phase
Displacement
Output Transients
Frequency Regulation
Synchronous to Bypass
Frequency Slew Rate
Overload Capability
Maximum Output Capability
76
125%
Ripple voltage less than 0.5% peak to peak
100% rated current at 0.8 power factor
1% (10% to 100% load)
208 VAC nominal, adjustable from 198 VAC
to 218 VAC (60 Hz only)
480 VAC nominal, adjustable from 456 VAC
to 504 VAC (60 Hz only)
600 VAC nominal, adjustable from 570 VAC
to 630 VAC (60 Hz only)
400 VAC nominal, adjustable from 380 VAC
to 420 VAC (50/60 Hz)
3% max THD, 2% max single (for linear load)
3% for 100% maximum load imbalance
3˚ for 100% maximum load imbalance
5% for 100% load step or removal
0.01 Hz free running
Bypass within voltage limits of +5%, ---8% of
output setting; bypass within 0.5 Hz
1 Hz per second maximum (adjustable)
1125% for 10 minutes
1150% for 10 seconds
300% peak for 10 cycles without bypass