Configuring The Modem; Basic Modem Configuration - Powerware 9315 Operation Manual

200 kva -- 300 kva
Hide thumbs Also See for 9315:
Table of Contents

Advertisement

Configuring the Modem

The modem must be configured by the user before connecting to the UPS. In
addition, the modem must be programmed with the Call Out telephone numbers in
order to operate the Remote Notification option.
To configure the modem, connect the serial port of a standard PC computer to
the modem through the serial cable. Run a terminal emulation program on the
computer. Test the connection to the modem by typing [A], [T] and [ENTER].
The modem should respond with either "OK" or "0" (zero). If the modem does not
respond, consult the modem manufacturer's manual to confirm your setup. If the
modem still does not respond, then seek technical assistance from your modem
manufacturer.
After connection, perform "Basic Modem Configuration" and the remaining
sections of this chapter.

Basic Modem Configuration

The basic modem configuration consists of establishing the default operating
parameters for the modem and saving them to the modem memory. This
procedure sets up the modem for all operations. The configuration procedure
is as follows:
1. Connect the modem to the PC through the serial port as described in the modem
manufacturer's manual.
NOTE: The brackets ([ ]) in the following steps indicate characters that require
keying in prior to pressing [ENTER].
2. Key in [A], [T], then press [ENTER].
3. Confirm that the modem responds with "OK" or "0" (zero).
4. Key in [A], [T], [&], [F], then press [ENTER].
5. Confirm that the modem responds with "OK" or "0" (zero).
6. Key in [A], [T], [Q], [0] (zero), [V], [0] (zero), [M], [0] (zero), [N], [0] (zero), [X],
[0] (zero), [&], [A], [0] (zero), [&], [D], [0] (zero), [&], [K], [0] (zero), [&], [Q], [5].
Verify that the display reads "ATQ0V0M0N0X0&A0&D0&K0&Q5", then press
[ENTER].
7. Confirm that the modem responds with "OK" or "0" (zero).
8. Key in [A], [T], [&], [W], [0] (zero), then press [ENTER].
9. Confirm that the modem responds with "OK" or "0" (zero).
10. Key in [A], [T], [&], [Y], [0] (zero), then press [ENTER].
11. Confirm that the modem responds with "OK" or "0" (zero).
62
Powerware 9315 (200 kVA ---300 kVA) Operation
164201036 Rev. D 041500