Relay Interface Module

An optional Relay Interface Module (RIM) uses relay contact closures to indicate
the operating status and alarm condition of the UPS system. A maximum of two
monitoring accessories (RMPs, RIMs, or SCMs) can be installed. See Table 1 for
the number of accessories permitted. Figure 21 shows the RIM with its four 15-pin
connectors labeled J1 through J4.
The RIM can provide these signals:
·
UPS AVAILABLE
·
UPS OFF LINE
·
UTILITY FAILURE
·
BATTERY WEAK
36

Figure 21. Relay Interface Module

(pins 1 and 12) Contacts are closed when the UPS is
offline.
(pins 3 and 13) Contacts are closed when the UPS is
operating in Normal mode.
(pins 6 and 15) Contacts are closed when Utility Failure is
detected.
(pins 5 and 14) Contacts are closed when approximately
2 minutes of battery time is remaining, before the critical
load is lost.
Powerware 9315 (200 kVA ---300 kVA) Operation
164201036 Rev. D 041500