Figure 13; Meters Printout (Ctrl + M); Figure 13---5. System Meters Screen; System Information Printout (Ctrl + A) - Powerware 9315s Installation & Operation Manual

Parallel capacity/redundant ups with powerhandler plus switchboard system bypass module (ssbm)
Table of Contents

Advertisement

13.5.3

Meters Printout (Ctrl + M)

This key sequence prints the current readings of the SSBM system meters. The
Input area shows the phase-to-phase voltage, frequency, and phase current of the
incoming utility, followed by the kVA, kW, and power factor measurements. The
output area shows the same information for the power being output by the SSBM.
The Bypass area shows the phase-to-phase voltage of the bypass source. The
Battery area displays the DC voltage (V) and the DC current (I). Figure 13---5
shows a sample Meters printout.
UPS System Normal
Alarm:
Notice:
13.5.4

System Information Printout (Ctrl + A)

This key sequence prints a listing of all available serial data. This printout contains
the information shown on the Event History Log and Meters screens of the SSBM
(both Figures 13---4 and 13---5).
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A
092402
Uninterruptible Power System
None
None
Input
VAB
VBC VCA
FREQ
480
480 480
60.0
IA
IB
IC
640
640
640
KVA
KW
PF
530
505
0.95
Bypass
VAB
VBC
VCA
480
480
480

Figure 13---5. System Meters Screen

03 NOV 1997
Output
VAB
VBC
VCA
FREQ
480
480
480
60.0
IA
IB
IC
IN
480
480
480
0
KVA
KW
PF
400
320
0.80
Battery
V
I
+
540
0
14:22:45
13--9

Advertisement