Figure 15; Meters Printout (Ctrl + M); System Information Printout (Ctrl + A) - Powerware Uninterruptible Power Supply Installation And Operation Manual

Uninterruptible power supply 500 kva -- 750 kva
Table of Contents

Advertisement

15.5.3 Meters Printout (Ctrl + M)

This key sequence prints the current readings of the UPS system meters. The
Input area shows the phase-to-phase voltage, frequency, and phase current of the
incoming utility, followed by the kVA, kW, and power factor measurements. The
output area shows the same information for the power being output by the UPS.
The Bypass area shows the phase-to-phase voltage of the bypass source. The
Battery area displays the DC voltage (V) and the DC current (I). Figure 15---5
shows a sample Meters printout.
UPS System Normal
Alarm:
Notice:

15.5.4 System Information Printout (Ctrl + A)

This key sequence prints a listing of all available serial data. This printout contains
the information shown on the Event History Log and Meters screens of the UPS
(both Figures 15---4 and 15---5).
Powerware 9315 (500 kVA- -750 kVA) Installation and Operation
164201244 REV. D 030101
Uninterruptible Power System
None
None
Input
VAB
VBC VCA
FREQ
480
480 480
60.0
IA
IB
IC
640
640
640
KVA
KW
PF
530
505
0.95
Bypass
VAB
VBC
VCA
480
480
480
Figure 15 ---5. System Meters Screen
03 NOV 1997
Output
VAB
VBC
VCA
FREQ
480
480
480
60.0
IA
IB
IC
IN
480
480
480
0
KVA
KW
PF
400
320
0.80
Battery
V
I
+
540
0
14:22:45
15--9

Advertisement

Table of Contents
loading

This manual is also suitable for:

9315

Table of Contents