Drive Control Via Bacnet Ms/Tp - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

6.9

Drive control via BACnet MS/TP

Settings for BACnet MS/TP
Parameter
p2020
p2021
p2024
p2025
p2026
r2029
p2030 = 5
Control word 1 (STW1)
Bit
0
1
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Explanation
Fieldbus interface bau‐
drate (Factory setting: 6)
Fieldbus interface address (Factory setting: 1)
Valid USS addresses: 0 ... 127.
The parameter is only active if address 0 is set at the Control Unit address switch.
A change only becomes active after the inverter power supply is switched off and switched
on again.
Fieldbus interface times [0] maximum permissible processing time (APDU timeout)
Fieldbus SS BACnet
settings
Fieldbus interface BACnet COV increment
Change in value at which point the inverter sends and UnConfirmedCOVNotification or
and ConfirmedCOVNotification.
Fieldbus interface error
statistics
Fieldbus interface protocol selection
p0015 = 110 sets p2013 = 5 → BACnet MS/TP
Meaning
0 = OFF1
0 → 1 = ON
0 = OFF2
1 = No OFF2
6: 9600 baud
7: 19200 baud
[0] = device object instance number
[1] = info maximum number frames
[2] = APDU number of retries
[3] = maximum master address
[0] number of error-free tele‐
grams
[1] number of rejected tele‐
grams
[2] number of framing errors
[3] number of overrun errors
Explanation
The motor brakes with the ramp-down
time p1121 of the ramp-function gen‐
erator. The inverter switches off the
motor at standstill.
The inverter goes into the "ready"
state. If, in addition bit 3 = 1, then the
inverter switches on the motor.
Switch off the motor immediately, the
motor then coasts down to a standstill.
The motor can be switched on (ON
command).
Advanced commissioning
6.9 Drive control via BACnet MS/TP
8: 38400 baud
10: 76800 baud
[4] number of parity errors
[5] number of starting charac‐
ter errors
[6] number of checksum errors
[7] number of length errors
BACNet
Signal inter‐
connection in
the inverter
BV20
p0840[0] =
r2090.0
BV27
p0844[0] =
r2090.1
241