Number
Cause
F07896
Load monitoring, pump leakage
F07900
Motor blocked
F07901
Motor overspeed
F07902
Motor stalled
A07903
Motor speed deviation
A07910
Motor overtemperature
A07920
Torque/speed too low
A07921
Torque/speed too high
A07922
Torque/speed out of tolerance
F07923
Torque/speed too low
F07924
Torque/speed too high
A07927
DC braking active
A07980
Rotary measurement activated
A07981
No enabling for rotary measurement Acknowledge pending faults.
A07991
Motor identification activated
F08501
Setpoint timeout
F08502
Monitoring time, sign-of-life expired ● Check the PROFINET connection.
F08510
Send configuration data not valid
A08511
Receive configuration data not valid
A08526
No cyclic connection
A08565
Consistency error affecting adjusta‐
ble parameters
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Remedy
● Rectify the leakage in the pump circuit.
● For a false tripping, reduce the torque thresholds of the leakage
characteristic (p2186, p2188, p2190).
Check that the motor can run freely.
Check the torque limits (r1538 and r1539).
Check the parameters of the "Motor blocked" message (p2175, p2177).
Activate the precontrol for the speed limiting controller (p1401 bit 7 = 1).
Increase the hysteresis for overspeed signal p2162.
Check whether the motor data has been set correctly and perform a motor
identification.
Check the current limits (p0640, r0067, r0289). If the current limits are too
low, the drive cannot be magnetized.
Check whether motor cables are disconnected during operation.
Increase p2163 and/or p2166.
Increase the torque, current and power limits.
Check the motor load.
Check the motor's ambient temperature.
Check the KTY84 or PT1000 sensor.
Check the overtemperatures of the thermal model (p0626 ... p0628).
The torque deviates from the torque/speed envelope curve.
● Check the connection between the motor and the load.
● Adapt the parameterization corresponding to the load.
● Check the connection between the motor and the load.
● Adapt the parameterization corresponding to the load.
Not required
Not required
Establish missing enables (see r00002, r0046).
Switch on the motor and identify the motor data.
● Check the PROFINET connection.
● Set the controller to RUN mode.
● If the fault occurs repeatedly, check the monitoring time set p2044.
● Check the PROFINET configuration
● Activate the control with cyclic operation.
● Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
Check the following:
● IP address, subnet mask or default gateway is not correct.
● IP address or station name used twice in the network.
● Station name contains invalid characters.
Alarms, faults and system messages
8.6 List of alarms and faults
411