Commissioning
5.5 Quick commissioning with a PC
Select the suitable application class
When selecting an application class, the inverter assigns the appropriate settings to the motor
control.
Application class
Properties
● Typical settling time after a speed change:
● Typical settling time after a load surge: 500 ms
● Standard Drive Control is suitable for the
● Standard Drive Control is insensitive with
Application exam‐
● Pumps, fans, and compressors with flow
ples
Power Modules
that can be operat‐
ed
Max. output fre‐
quency
Motors that can be
operated
Commissioning
● Unlike "Dynamic Drive Control," no speed
● Compared with the "EXPERT" setting:
● Standard Drive Control is preset for Power
180
Standard Drive Control
100 ms ... 200 ms
following requirements:
Motor power ratings < 45 kW
Ramp-up time 0 → rated speed
(depending on the motor power rating):
1 s (0.1 kW) ... 10 s (45 kW)
Applications with increasing load torque
without load surges
respect to imprecise setting of the motor data
characteristic
PM240‑2, PM240P-2
550 Hz
Induction motors
controller needs to be set
Simplified commissioning using
predefined motor data
Reduced number of parameters
Modules, frame size A ... frame size C
Dynamic Drive Control
● Typical settling time after a speed change:
< 100 ms
● Typical settling time after a load surge: 200 ms
● Dynamic Drive Control controls and limits the
motor torque
● Torque accuracy that can be achieved: ± 5% for
15 % ... 100 % of the rated speed
● We recommend Dynamic Drive Control for the
following applications:
Motor power ratings > 11 kW
For load surges 10 % ... >100 % of the rated
motor torque
● Dynamic Drive Control is necessary for a ramp-
up time 0 → rated speed (dependent on the rated
motor power): < 1 s (0.1 kW) ... < 10 s (132 kW).
● Pumps and compressors with displacement
machines
PM240‑2, PM240P-2
240 Hz
Induction, synchronous and reluctance motors
● Fewer parameters compared with the
"EXPERT" setting
● Dynamic Drive Control is preset for Frame
Size D ... Frame Size JX Power Modules
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE