Siemens SINAMICS G120 Operating Instructions Manual page 243

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Status word 1 (ZSW1)
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
If you change over from another telegram to telegram 20, then the assignment of the previous
1)
telegram is kept.
Further information
You can find additional information about BACnet MS/TP in the "Fieldbus" function manual:
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Meaning
1 = Ready to start
1 = Ready
1 = Operation enabled
1 = Fault active
1 = OFF2 inactive
1 = OFF3 inactive
1 = Closing lockout active
1 = Alarm active
1 = Speed deviation within the tol‐
erance range
1 = Master control requested
1 = Comparison speed reached or
exceeded
1 = Torque limit not reached
Reserved
0 = Alarm, motor overtemperature --
1 = Motor rotates clockwise
0 = Motor rotates counterclockwise Internal inverter actual value < 0
0 = Alarm, inverter thermal over‐
load
Overview of the manuals (Page 537).
6.9 Drive control via BACnet MS/TP
Remarks
Power supply switched on; electron‐
ics initialized; pulses locked.
Motor is switched on (ON/
OFF1 = 1), no fault is active. With
the command "Enable operation"
(STW1.3), the inverter switches on
the motor.
Motor follows setpoint. See control
word 1, bit 3.
The inverter has a fault. Acknowl‐
edge fault using STW1.7.
Coast down to standstill is not ac‐
tive.
Quick stop is not active.
It is only possible to switch on the
motor after an OFF1 followed by
ON.
Motor remains switched on; no ac‐
knowledgement is necessary.
Setpoint / actual value deviation
within the tolerance range.
The automation system is reques‐
ted to accept the inverter control.
Speed is greater than or equal to
the corresponding maximum speed.
Comparison value for current or tor‐
que has been fallen below.
Internal inverter actual value > 0
Advanced commissioning
Signal interconnection
in the inverter
p2080[0] = r0899.0
p2080[1] = r0899.1
p2080[2] = r0899.2
p2080[3] = r2139.3
p2080[4] = r0899.4
p2080[5] = r0899.5
p2080[6] = r0899.6
p2080[7] = r2139.7
p2080[8] = r2197.7
p2080[9] = r0899.9
p2080[10] = r2199.1
p2080[11] = r0056.13 /
r1407.7
p2080[12] = r0899.12
p2080[13] = r2135.14
p2080[14] = r2197.3
p2080[15] = r2135.15
243