Connecting The Inverter With The Pm230 Power Module Ip55 - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

4.4.5

Connecting the inverter with the PM230 Power Module IP55

Figure 4-11
Table 4-26
Inverters
FSA
FSB
FSC
FSD
FSE
FSF
EMC cable glands
To meet the requirements of degree of protection IP55/UL, type 12, and to fulfill EMC
requirements, adhere to the following:
● Use EMC cable glands for the control cables.
● Make sure that the cable glands match the drill holes in the plate.
Figure 4-12
The EMC cable glands are not included in the scope of supply of the inverter. Rubber sleeves
for unused drill holes in the cable cover plate are included in the scope of supply.
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
PM230 Power Module IP55 connection overview
Connection types, maximum conductor cross-sections and tightening torques
Connection
Terminal
1 ... 2.5 mm
Terminal
2.5 ... 6 mm
Terminal
6 ...16 mm
Cable lug
10 ... 35 mm
Cable lug
25 ... 50 mm
Cable lug
35 ... 120 mm
Example of an EMC cable gland (Blueglobe)
4.4 Connecting the line supply and motor
Cross-section / tightening torque
/ 0.5 Nm
18 ... 14 AWG / 4.4 lbf in
2
/ 0.6 Nm
14 ... 10 AWG, 5.3 lbf in
2
/ 1.5 Nm
10 ... 5 AWG / 13.3 lbf in
2
/ 6 Nm
5 ... 2 AWG / 53 lbf in
2
/ 6 Nm
3 ... 2 AWG / 53 lbf in
2
/ 13 Nm
2 ... 4/0 AWG, 115 lbf in
2
Installing
89