Technical data
10.6 Technical data, PM240-2 Power Module
Table 10-58 PM240-2, IP20, Frame Size D, 3-ph. AC 380 V ... 480 V
Article number without filter
Article number with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC/UL
Fuse according to IEC/UL, Class J
Power loss without filter
Power loss with filter
Required cooling air flow
Weight without filter
Weight with filter
Table 10-59 PM240-2, PT, frame size D, 3 AC 380 V ... 480 V
Article number without filter
Article number with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC/UL
Fuse according to IEC/UL, Class J
Power loss without filter
Power loss with filter
Required cooling air flow
Weight without filter
Weight with filter
Approx. 1 kW through the heatsink
1)
492
6SL3210-1PE27-5UL0
6SL3210-1PE27-5AL0
37 kW
70 A
75 A
30 kW
62 A
60 A
3NA3830 (100 A)
100 A
1.09 kW
1.10 kW
55 l/s
17 kg
18.5 kg
6SL3211-1PE27-5UL0
6SL3211-1PE27-5AL0
37 kW
70 A
75 A
30 kW
62 A
60 A
3NA3830 (100 A)
100 A
1.09 kW
1)
1.10 kW
1)
55 l/s
20 kg
21.5 kg