Advanced commissioning
6.3 Adapt the default setting of the terminal strip
The switch that belongs to the analog input is located behind the front doors of the Control
Unit.
● The switches for AI 0 and AI 1 (current/voltage) are located behind the lower
front door of the Control Unit.
● The switch for AI 2 (temperature/current) is located behind the upper front
door of the Control Unit.
Permissible measuring range of the temperature sensors
LG-Ni1000, DIN-Ni1000
Pt1000
For values outside the permissible measuring range, the inverter outputs Alarm A03520
"Temperature sensor fault".
Characteristics
If you change the analog input type using p0756, then the inverter automatically selects the
appropriate scaling of the analog input. The linear scaling characteristic is defined using two
points (p0757, p0758) and (p0759, p0760). Parameters p0757 ... p0760 are assigned to an
analog input via their index, e.g. parameters p0757[0] ... p0760[0] belong to analog input 0.
Figure 6-4
Parameter
p0757
p0758
p0759
p0760
p0761
204
– 88 °C ... 165 °C
– 88 °C ... 240 °C
Examples for scaling characteristics
Description
x coordinate of the 1st characteristic point [p0756 defines the unit]
y coordinate of the 1st characteristic point [% of p200x]
p200x are the parameters of the reference variables, e.g. p2000 is the reference speed
x coordinate of the 2nd point characteristic point [p0756 defines the unit]
y coordinate of the 2nd characteristic point [% of p200x]
Wire breakage monitoring response threshold
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE