Installing
4.4 Connecting the line supply and motor
Figure 4-26
Table 4-29
Connection, cross-section and tightening torque for PM240-2 Power Modules
Inverters
FSA
Line supply, motor,
DC link and braking
FSB
resistor
FSC
FSD
Line supply, motor
and DC link
Braking resistor
FSE
Line supply, motor
and DC link
Braking resistor
FSF
Line supply, motor
and DC link
Braking resistor
100
Connection of the PM240-2 Power Module, 1 AC 200 V, FSD ... FSF
Connection
Plug connector
with screw termi‐
nals
Screw-type termi‐
nal
Screw-type termi‐
nal
Cable lug accord‐
ing to SN71322
Screw-type termi‐
nal
Cross-section, tightening torque
Metric
1.5 ... 2.5 mm
, 0.5 Nm
2
1.5 ... 6 mm
, 0.6 Nm
2
6 ...16 mm², 1.3 Nm
10 ... 35 mm
,
2
2.5 ... 4.5 Nm
2.5 ... 16 mm
,
2
1.2 ... 1.5 Nm
25 ... 70 mm
, 8 ... 10 Nm 6 ... 3/0 AWG, 88.5 lbf in 25 mm
2
10 ... 35 mm
,
2
2.5 ... 4.5 Nm
35 ... 2 × 120 mm
,
2
22 ... 25 Nm
25 ... 70 mm
, 8 ... 10 Nm 6 ... 3/0 AWG, 88.5 lbf in 25 mm
2
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Imperial
16 ... 14 AWG, 4.5 lbf in 8 mm
16 ... 10 AWG, 5.5 lbf in 8 mm
10 ... 6 AWG, 12 lbf in
20 ... 10 AWG, 22 lbf in
8 ... 2 AWG, 40 lbf in
20 ... 6 AWG, 15 lbf in
20 ... 10 AWG, 22 lbf in
8 ... 2 AWG, 40 lbf in
1 ... 2 × 4/0 AWG,
210 lbf.in
Converter with the CU230P-2 Control Units
Stripped
insulation
length
10 mm
18 mm
10 mm
18 mm
--