also results in a higher motor slip, which is proportional to the accelerating torque. I
I
controllers keep the motor flux constant using the output voltage, and adjust the matching
d
current component I
All of the function diagrams 6020 ff. for vector control are provided in the List Manual.
Settings that are required
In order to achieve a satisfactory control response, as a minimum you must set the partial
functions – shown with gray background in the diagram above – to match your particular
application:
● Motor and current model: In the quick commissioning, correctly set the motor data on the
rating plate corresponding to the connection type (Y/Δ), and carry out the motor data
identification routine at standstill.
● Speed limits and torque limits: In the quick commissioning, set the maximum speed (p1082)
and current limit (p0640) to match your particular application. When exiting quick
commissioning, the inverter calculates the torque and power limits corresponding to the
current limit. The actual torque limits are obtained from the converted current and power
limits and the set torque limits.
● Speed controller: Start the rotating measurement of the motor data identification. You must
manually optimize the controller if the rotating measurement is not possible.
Default settings after selecting the application class Dynamic Drive Control
Selecting application class Dynamic Drive Control adapts the structure of the vector control
and reduces the setting options:
Hold or set the integral component of the
speed controller
Acceleration model for precontrol
Motor data identification at standstill or with ro‐
tating measurement
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
in the motor.
q
Overview of the manuals (Page 537)
Vector control after se‐
Vector control without select‐
lecting the application
class Dynamic Drive
Control
Not possible
Default setting
Shortened, with option‐
al transition into opera‐
tion
Advanced commissioning
6.24 Motor control
and
q
ing an application class
Possible
Can be activated
Complete
307