Default setting 104: "ESM stairwell pressure control"
DO 0: p0730, ..., DO 2: p0732
Additional settings:
● Pressure control using the technology controller
● Analog inputs smoothing time constant: p0753 = 500 ms
● Technological unit: p0595 = 1 (%), reference variable: p0596 = 1
● Default setting of the technology controller:
● "Flying restart" is enabled: p1200 = 1
● Automatic restart is active. After a power failure, the inverter automatically acknowledges possible
Designation in the BOP-2: P_F Stw
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
–
Enable: p2200 = 1
–
Fixed value 1: p2201 = 40 %
–
Ramp-up/down time for setpoint: p2257 = p2258 = 30 s
–
Ramp-up/down time for controller output: p2293 = 30 s
–
Upper and lower limits, actual value: p2267 = 120 %, p2268 = -10 %
–
Actual value filter time constant: p2265 = 10 s
–
Proportional gain K
, integral time T
P
p2285 (T
) = 25 s, p2274 (T
I
–
Technology controller minimum limiting p2292 = 30 %
–
Technology controller output signal start value p2302 = 35 %
faults and switches on the motor: p1210 = 26
4.5 Connecting the interfaces for the inverter control
AO 0: p0771[0], AO 1: p0771[1]
, differentiation time constant T
I
) = 0 s
D
Installing
DI 0: r0722.0
AI 0: r0755[0]
: p2280 (K
) = 1.2,
D
P
123