13. Before making a service call
- Trip information and remedies
13.1 Trip /Alarm causes and remedies
When a problem arises, diagnose it in accordance with the following table.
If it is found that replacement of parts is required or the problem cannot be solved by any remedy described in the
table, contact your Toshiba distributor.
[Trip information]
Error code
Failure code
0001
0002
0003
0004
0005
*
0008
*
0009
000A
* This marking trips can be selected valid or invalid by parameters.
Problem
Overcurrent during
The acceleration time is too short.
acceleration
The V/F setting is improper.
A restart signal is input to the rotating
motor after a momentary stop, etc.
A special motor (e.g. motor with a small
impedance) is used.
Low inductance motor especially High
speed motor is used.
Overcurrent during
The deceleration time is too short.
deceleration
Low inductance motor especially High
speed motor is used.
The load fluctuates abruptly.
Overcurrent during
constant speed
The load is in an abnormal condition.
operation
Low inductance motor especially High
speed motor is used.
Overcurrent (An
The insulation of the output main circuit or
overcurrent on the
motor is defective.
load side at start-up)
The motor has too small impedance.
Overcurrent at start-
A main circuit element is defective.
up
Input phase failure
A phase failure occured in the input line of
the main circuit.
The capacitor in the main circuit lacks
capacitance.
Output phase failure
A phase failure occurred in the output line
of the main circuit.
The motor has too big impedance.
Overvoltage during
The input voltage fluctuates abnormally.
acceleration
(1) The power supply has a capacity of
500kVA or more.
(2) A power factor improvement capacitor is
opened or closed.
(3) A system using a thyristor is connected
to the same power distribution line.
A restart signal is input to the rotating
motor after a momentary stop, etc.
Possible causes
Increase the acceleration time .
Check the V/F parameter setting.
Use (auto-restart) and
In case of pt=0, 1, 7, decrease vb.
In case of pt=2 to 6, set f415
Choose the higher power range drive.
(1 class up drive is recommended.)
Increase the deceleration time .
Choose the higher power range drive.
(1 class up drive is recommended.)
Reduce the load fluctuation.
Check the load (operated machine).
Choose the higher power range drive.
(1 class up drive is recommended.)
Check the secondary wiring and insulation
Set f613=2, 3
Contact your Toshiba distributor.
Check the main circuit input line for phase
Check the capacitor in the main circuit for
Check the main circuit output line, motor,
Select output phase failure detection
Insert a suitable input reactor.
Use (auto-restart) and
M-1
E6581926
Remedies
(ride-through control).
(Motor rated current) and make an auto-
tuning.
state.
failure.
exhaustion.
etc. for phase failure.
parameter f605.
(ride-through control).
(Continued overleaf)