5.9
Auto-restart (Restart of coasting motor)
f301 : Auto-restart control selection
Stand clear of motors and mechanical equipment
If the motor stops due to a momentary power failure, the equipment will start suddenly when power is
restored.
Mandatory
This could result in unexpected injury.
action
Attach caution label about sudden restart after a momentary power failure on inverters, motors and
equipment for prevention of accidents in advance.
Function
The f301 parameter detects the rotating speed and rotational direction of the motor during coasting at
the event of momentary power failure, and then after power has been restored, restarts the motor
smoothly (motor speed search function). This parameter also allows switching from commercial power
5
operation to inverter operation without stopping the motor.
During operation, "rtry" is displayed.
[Parameter setting]
Title
f301
*
If the motor is restarted in retry mode, this function will operate, regardless of the setting of this parameter.
1)
Auto-restart after momentary power failure (Auto-restart function)
Setting f301 to 1 or 3: This function operates after power has been restored following detection of an
undervoltage by the main circuits and control power.
Function
Auto-restart control
selection
Input voltage
Motor speed
Forward / reverse
Caution
Adjustment range
0: Disabled
1: At auto-restart after momentary stop
2: At ST terminal off and on
3: 1 2
4: At start-up
ON
OFF
E-20
E6581926
Default setting
0