Toshiba Tosvert VF-S15 Instruction Manual page 63

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

(3) Coast stop
Assign parameters as described below in case of
Coast stop. Inverter will display off at Coast stop.
1) Assign "6 (ST)" to an input terminal. Set parameter
=. Open the ST-CC for coast stop(see the
status described on the right).
2) Assign "96 (FRR)" to an input terminal.
Coast stop is done by shorting FRR and CC.
3.1.2
3
[Example of fmod setting procedure] fmod=1: Setting the frequency by the terminal VIA
Panel operation
MODE
*Pressing the MODE key twice returns the display to standard monitor mode (displaying output frequency).
(1) Setting using the keypad or extension panel option (fmod=0 or 3)
For an extension panel option,
 Example of operating from the panel (=: press in center to save)
Panel operation
How to set the frequency
LED display
Displays the output frequency (operation stopped).
00
(When standard monitor display selection f710=0 [output frequency])
Displays the first basic parameter [History (auh)].
auh
Turn the setting dial, and select "fmod".
fmod
Press the center of the setting dial to read the parameter value.
0
(Standard default: 0).
Turn the setting dial to change the parameter value to  (terminal VIA).
1
The parameter value is written. fmod and the parameter value are
1fmod
displayed alternately several times.
: Moves the frequency up
key moves the frequency up,
LED display



Motor
speed
F-CC
ST-CC
Operation
: Moves the frequency down
Operation
Displays the output frequency.
(When standard monitor display selection = [output frequency])
Set the output frequency. (The frequency will not be saved if the
power is turned off in this state.)
Save the output frequency.  and the frequency are displayed
alternately.
C-4
E6581926
Coast stop
key moves the frequency down.
ON
OFF
ON
OFF

Hide quick links: