[Parameter setting]
Title
Function
Logic output/pulse train
f669
output selection (OUT)
Pulse train output function
f676
selection (OUT)
Maximum numbers of
f677
pulse train output
f678 Pulse train output filter
Digital panel meter for reference
Type: K3MA-F (OMRON)
Connection terminal: OUT-E4, NO-E5
Note 1: When item of f676 reaches "Reference of max. value", the number of pulse train set by f677
are sent to output terminals (OUT)
Note 2: The ON pulse width is maintained constant.
The ON pulse width is fixed at a width that causes the duty to reach 50% at the maximum pulse
number set with f677 .
Therefore, the duty is variable.
For example, the ON pulse width is
Note 3: The minimum pulse output rate is 10pps. Keep in mind that no pulses can be put out at any rate
smaller than this.
Note 4: f676 = 12 is the motor drive frequency.
Adjustment range
0: Logic output
1: Pulse train output
0: Output frequency
1: Output current
2: Frequency command value
3: Input voltage (DC detection)
4: Output voltage (command value)
5: Input power
6: Output power
7: Torque
8: -
9: Motor cumulative load factor
10: Inverter cumulative load factor
11: PBR (Braking resistor) cumulative
load factor
12: Stator frequency
13: VIA input value
14: VIB input value
15: Fixed output 1
(output current 100% equivalent)
16: Fixed output 2
(output current 50% equivalent)
17: Fixed output 3
(Other than the output current)
18: Communication data
19: -
20: VIC input value
21, 22: -
23: PID feedback value
0.50-2.00 (kpps)
2-1000 (ms)
approximately 0.6 ms when f677 = 0.80 (pps)
approximately 0.5 ms when f677 = 1.00 (pps)
approximately 0.3 ms when f677 = 1.60 (pps)
F-119
E6581926
Reference
Default
of maximum
setting
value of
f677
–
0
fh
185%
fh
150%
150%
185%
185%
250%
-
100%
100%
100%
fh
0
10 V
10 V
6
185%
185%
100%
100.0%
-
20mA
-
100%
–
0.80
–
64